   BOP 1 KILOWATT PROGRAMMING/DISPLAY CHARACTERISTICS
SPECIFICATION RATING DESCRIPTION
Trigger
Port
pin 2
shutdown (pin 2) has three functions:    
external trigger
shutdown default
Isolated input far setting the BOP in STANDBY (output off) (latched status) Pulse width: 100 microseconds min.
Action delay: 200 microseconds max.
Restore operation by pressing STANDBY key(1) or sending OUTP ON command via remote interface.
output on-off
control input
Isolated input for controlling output status, on or off Action delay: 100 μS max.
Signal logic established by 0UTP:CONT command or from front panel
disabled Disables external trigger shutdown and output on-off control input  
Trigger
Port
pin 4
external trigger input (pin 4) lsolated input for trigger events Pulse width: 100 microseconds min.
Action delay: 500 microseconds max.
Digital
Control
local Panel-mounted keypad(1) Direct entry
remote IEEE 488-2 (GPIB) SCPI
remote RS 232 SCPI
remote LXI Ethernet (LAN) SCPI
remote RS 485 (BITBUS) Used for series and parallel configurations
Display(1) front panel 4.7 inch backlit 16-bit color LCD, displays all functions  
remote
(MG and GL)
All parameters read back on RS 232 and GPIB buses  
remote
(ME and EL)
All parameters read back on LAN and RS 232 ports  
(1) References to keypad and display apply only to MG and ME models.