Follow @kepco_careers
Advanced Search
Kepco Power Solutions
718-461-7000
   BOP 1 KILOWATT SERIES (MG, ME SUFFIX) MODEL TABLE
MODEL (1) d-c OUTPUT RANGE CLOSED LOOP GAIN OUTPUT IMPEDANCE
EO MAX. (2)
(V d-c)
IO MAX.
(A d-c)
VOLTAGE
CHANNEL
GV (V/V)
CURRENT
CHANNEL
GI (A/V)
VOLTAGE MODE CURRENT MODE
SERIES R
(mΩ)
SERIES L
(µH)
SHUNT R
(Ω)
SHUNT C
(µF)
1000 WATT
BOP 6-125MG or ME 0 to ±6 0 to ±125 0.6 12.5 0.05 1.5 24 1150
BOP 10-100MG or ME 0 to ±10 0 to ±100 1.0 10.0 0.1 2.0 50 1100
BOP 10-75MG or ME 0 to ±10 0 to ±75 1.0 7.5 0.13 2.0 67 976
BOP 20-50MG or ME 0 to ±20 0 to ±50 2.0 5.0 0.40 8.3 200 371
BOP 25-40MG or ME 0 to ±25 0 to ±40 2.5 4.0 0.63 15.8 313 165
BOP 36-28MG or ME 0 to ±36 0 to ±28 3.6 2.8 1.30 25 640 103
BOP 50-20MG or ME 0 to ±50 0 to ±20 5.0 2.0 2.50 50 1250 55
BOP 72-14MG or ME 0 to ±72 0 to ±14 7.2 1.4 5.14 104 2570 33
BOP 100-10MG or ME 0 to ±100 0 to ±10 10.0 1.0 10.0 163 5000 16
(1) Models with MG suffix include built-in standard GPIB and RS 232 digital interfaces.
Models with ME suffix include built-in standard LXI Ethernet (LAN) and RS 232 digital interfaces.
(2) When connecting active loads, the steady-state voltage of the active load must not exceed the maximum voltage rating of the BOP. Otherwise the overvoltage protection will shut down the power supply.

   BOP 1 KILOWATT SERIES (GL, EL SUFFIX) MODEL TABLE
MODEL (1) d-c OUTPUT RANGE (2) CLOSED LOOP GAIN RIPPLE AND NOISE
EO MAX. (3)
(V d-c)
IO MAX.
(A d-c)
VOLTAGE
CHANNEL
GV (V/V)
CURRENT
CHANNEL
GI (A/V)
VOLTAGE MODE CURRENT MODE
1000 WATT
BOP 10-100GL or EL 0 to ±10 0 to ±100 1.0 10.0 0.02% 0.01%
BOP 20-50GL or EL 0 to ±20 0 to ±50 2.0 5.0 0.02% 0.01%
BOP 36-28GL or EL 0 to ±36 0 to ±28 3.6 2.8 0.02% 0.01%
BOP 50-20GL or EL 0 to ±50 0 to ±20 5.0 2.0 0.02% 0.01%
(1) Models with GL suffix include built-in standard GPIB and RS 232 digital interfaces.
Models with EL suffix include built-in standard LXI Ethernet (LAN) and RS 232 digital interfaces.
(2) For other Volt-Ampere combinations, please consult factory.
(3) When connecting active loads, the steady-state voltage of the active load must not exceed the maximum voltage rating of the BOP. Otherwise the overvoltage protection will shut down the power supply.
PREVIOUS TOP NEXT

Products Support Literature Contact Us Careers About

KEPCO, INC. 131-38 SANFORD AVENUE FLUSHING, NY. 11355 U.S.A.
TEL (718) 461-7000 FAX (718) 767-1102
www.kepcopower.com email: hq@kepcopower.com