BOP 1 KILOWATT INPUT CHARACTERISTICS
|
SPECIFICATION
|
RATING/DESCRIPTION
|
CONDITION
|
a-c voltage |
Nominal |
200/220/230/240Va-c (1)) (200-240 Va-c) |
No setting required. Single phase or between 2 phases of a 3-phase system within 200-240Va-c. |
Range |
176-264V a-c
|
Frequency |
Nominal |
50/60 Hz |
|
Range |
47 - 63 Hz
|
Current |
176V a-c |
9.5A (7.5A (2)) |
Maximum |
264V a-c |
6.4A (4.4A (2)) |
Maximum |
Power Factor |
Source |
0.99 |
Nominal output power |
Sink |
0.97 |
Efficiency |
Source |
65% to 75%
(model dependent)
56%/65% (3)
|
Minimum value, @Nominal sourced output power (V-I quadrant 1 & 3) |
Sink |
50% to 65% (model dependent) 45%/43% (3)
|
Minimum value, @Nominal sink output power (V-I quadrant 2 & 4) |
Switching Frequency |
70 KHz ±5% (50 KHz ±5% (2)) |
Active PFC for source and sink. |
EMC Compliance |
EN 61326-1 (1997) |
Class A equipment |
EMC Immunity |
ESD |
EN61000-4-2 |
Electrostatic discharge |
Radiated RF |
EN61000-4-3 |
|
EFT |
EN61000-4-4 |
Electrical fast transient/burst |
Surges |
EN61000-4-5 |
|
Conducted RF |
EN61000-4-6 |
|
EMC Emissions |
Conducted |
EN61000-3-2 |
Harmonics |
EN61000-3-4 |
Fluctuation and flicker |
Conducted |
EN55011/CISPR11 |
0.15 to 30 MHz |
Radiated |
EN55011/CISPR11 |
30 to 1000 MHz |
Leakage Current |
3.5 mA |
230V a-c, 47 - 63Hz |
Insulation Coordination |
Input |
Installation Category II |
For TN or TT Power System |
Overvoltage Category II |
Output |
Installation Category II |
Maximum 300V (500V for 10V models) common mode voltage between output terminals and chassis ground |
Overvoltage Category II |
Pollution Degree |
2 |
|