KLN SERIES PROGRAMMING CHARACTERISTICS
DIGITAL: 5KW, 10KW, 15KW
|
Specification
|
Rating/Description
|
Programming accuracy (1)
|
Voltage:
|
±(0.1% of rated voltage + 2 digits)
|
Current:
|
±(0.2% of rated current + 2 digits)
|
Power:
|
±(0.1% of rated power + 2 digits)
|
Measurement accuracy (1)
|
Voltage:
|
±(0.1% of rated voltage + 2 digits)
|
Current:
|
±(0.2% of rated current + 2 digits)
|
Power:
|
±(0.2% of rated power + 2 digits)
|
Command Response Time
|
< 10mS after received, LAN interface (2)
|
LAN (LXI) digital interface
|
Standard, built-in to all models
|
GPIB IEEE 488.2 digital interface
|
Optional (G suffix), added to standard inferface
|
USB digital interface (3)
|
Optional (U suffix), added to standard inferface
|
Serial Port digital interface (RS 485/RS 422) digital interface (3)
|
(Optional - S Suffix) added to standard inferface
Default baud rate: 115.2K, Max baud rate: 115.2K
Max number of units connected to bus: 254
Max effective control distance: 1000 meters
|
Programming interface
|
IVI-COM driver provided, SCPI commands supported
|
User-programmed
Memory Locations
|
8000 sets, each capable of storing Voltage, Current, Power and Time (0.1mS min).
USB port provided for convenient loading of memory locations.
Three sets can be stored/recalled from front panel.
|
Programmable
Output Ramp
|
Ramp up time:
|
Adjustable range 0.1 to 99.9 Sec
|
Ramp down time:
|
Adjustable range 0.1 to 99.9 Sec |
User-programmable
Sequences
|
8000 steps (max.)
Step time adjustable range 0.00Sec to 99,999 hours
|