Follow @kepco_careers
Advanced Search
Kepco Power Solutions
718-461-7000
   KLN SERIES OUTPUT CHARACTERISTICS: 750W, 1500W, 3000W
Specification Rating/Description
Type of Stablizer   Constant Voltage (CV) / Constant Current (CC),
automatic crossover
Adjustment Range Voltage: 0 to 100% of rated voltage
Current: 0 to 100% of rated current
Protective functions  
Programmable overvoltage (OVP)
Programmable overcurrent (OCP)
Overtemperature (OTP)
Fuse blown
Protection setting range Overvoltage: 0 to 110% of rated voltage
Overcurrent: 10 to 110% of rated current
Parallel Operation   Up to 5 units maximum, automatic load sharing
Current Sharing Tolerance: 1% at rated current, 5% at 50% of rated current,
10% at less than 10% of rated current
Series Operation   2 units maximum (total voltage must not exceed 600V)
Temperature. Coefficient 100ppm/°C of rated output Voltage or Current, after 30 minute warm-up
Temperature Drift   0.05% of rated Vout (CV) or Aout (CC) over 8hrs interval following 30 minutes warm-up. Constant line, load and temperature.
Transient
response time
(Constant Voltage mode)
20V and under: ≤1.5ms
30V~100V: ≤1ms
150V~600V: ≤2ms
Hold-up Time   20ms

PREVIOUS TOP NEXT

ProductsSupportLiteratureContact UsCareersAbout

KEPCO, INC. • 131-38 SANFORD AVENUE • FLUSHING, NY. 11355 U.S.A.
TEL (718) 461-7000 • FAX (718) 767-1102
www.kepcopower.com • email: hq@kepcopower.com