KLN SERIES OUTPUT CHARACTERISTICS: 5KW, 10KW, 15KW |
Specification
|
Rating/Description
|
Type of Stablizer
|
|
Constant Voltage (CV) / Constant Current (CC), auto crossover (1)
|
Adjustment Range
|
Voltage:
|
0 to 105% of rated voltage
|
Current:
|
0 to 105% of rated current
|
Protective functions
|
|
Programmable overvoltage (OVP)
Programmable overcurrent (OCP)
Overtemperature (OTP)
Source Power Fail |
Protection setting range
|
Overvoltage:
|
0 to 110% of rated voltage
|
Overcurrent:
|
0 to 110% of rated current |
Remote Error Sense Compensation
|
5V max.
|
Source Effect
|
Voltage:
|
±0.02% of rated voltage (2)
|
Current:
|
±0.05% of rated current (2)
|
Power:
|
±0.05% of maximum power (2)
|
Load Effect
|
Voltage:
|
±0.05% of rated voltage (3)
|
Current:
|
±0.15% of rated current (4)
|
Power:
|
±0.75% of maximum power (5)
|
Parallel Operation
|
|
Up to 10 units maximum, automatic load sharing
|
Series Operation
|
|
2 units maximum
|
Temperature. Coefficient
|
100ppm/°C of rated output Voltage or Current, after 30 minute warm-up
|
Response time
|
Full load (up)
|
<0.03 Sec
|
Full load (down)
|
<0.08 Sec
|
No load (down)
|
80V to 350V: <30 Sec
250V and higher: 10 Sec |
Transient response time (6) (Constant Voltage mode)
|
80V:
|
≤1.5ms
|
250V~650V:
|
≤2ms
|
1000V~1500V:
|
≤3ms |
Ground Polarity
|
Either positive or negative ground
|