Follow @kepco_careers
Advanced Search
Kepco Power Solutions
718-461-7000

   KLR PROGRAMMING CHARACTERISTICS (LOCAL)
Specification Rating/Description Condition
Local control Rotary encoders Panel mounted.
Local
control
resolution
Coarse: ~100 LSB/step Depress control for Fine resolution
Fine: 1 LSB/step
Setting range 0-100% of rating  
Power up
settings
voltage: defaults to zero KLR can save last setpoint values for voltage and current prior to unit shutdown, and recall them when unit is next turned on.
current: defaults to min. value
Protection
Limits
Overvoltage: 20-120% of Emax Programmable; accessed via front panel protect switch or SCPI command over digital bus.
Overcurrent: 72-120% of Imax

PREVIOUS TOP NEXT

ProductsSupportLiteratureContact UsCareersAbout

KEPCO, INC. • 131-38 SANFORD AVENUE • FLUSHING, NY. 11355 U.S.A.
TEL (718) 461-7000 • FAX (718) 767-1102
www.kepcopower.com • email: hq@kepcopower.com