KLR GENERAL SPECIFICATIONS
|
Specification
|
Rating/Description
|
Condition
|
Temperature |
Operating: |
-10 to +50°C
|
Rated load.
|
+50 to +70°C
|
Derate current 3% per °C over 50°C
|
Storage: |
-40 to +85°C
|
|
Cooling
|
3 internal d-c fans
|
exhaust to the rear
|
Humidity
|
0 to 95% RH
|
non-condensing
|
Shock
|
20g, 11msec ± 50% half sine
|
non-operating
|
Vibration |
5 -10 Hz: |
10mm double amplitude
|
3-axes, non-operating
|
10-55 Hz: |
2g
|
3-axes, non-operating
|
Altitude
|
sea level to 10000 ft.
|
0-3,000 ft: 100%, linear derating to 70% of power at 10,000ft.
|
Loss of source power
|
Shutdown
|
User selectable recovery (1)
|
Overtemperature protection
|
Shutdown
|
User selectable recovery (1)
|
Fan Failure
|
Shutdown
|
Recovery requires power recycling
|
(1) |
Either PROTECTED (output disabled and locked until source power recycled) or SAFE (output disabled with unit programmed to last setting; power recycling not needed for recovery) or AUTO (when fault clears, unit automatically recovers to programming setpoints and output state (enabled/disabled) as before fault was detected.
|
|