   KLP PROGRAMMING CHARACTERISTICS (LOCAL)
Specification Rating/Description Condition
Local control Rotary encoders Panel mounted.
Local
control
resolution
Coarse: ~100 LSB/step Depress control for Fine resolution
Fine: 1 LSB/step
Setting range 0-100% of rating KLP will automatically adjust limit to maintain 1200W maximum.
Power up
settings
voltage: defaults to zero KLP can save last setpoint values for voltage and current prior to unit shutdown, and recall them when unit is next turned on.
current: defaults to min. value
Protection
Limits
Overvoltage: 20-120% of Emax Programmable; accessed via front panel protect switch or SCPI command over digital bus.
Overcurrent: 72-120% of Imax