SERIES HSP OUTPUT CHARACTERISTICS
|
Specification
|
Rating/Description
|
Condition
|
Output setting range |
all except 48V: |
-80% to +10% (1)
|
Of nominal output
|
48V only: |
-80% to +25% (1)
|
Source Effect |
Typical: |
0.05%
|
Nominal ±15%
|
Maximum: |
0.1%
|
Load Effect |
Typical: |
0.05%
|
5 ~ 100% load; operation between 0 - 5% load results in increased ripple and degraded transient response.
|
Maximum: |
0.1%
|
Temperature Effect |
Typical: |
0.01%
|
Per °C (0 to 50°C)
|
Maximum: |
0.02%
|
Time Effect (drift) |
Typical: |
0.05%
|
0.5 ~ 8.5 hrs
|
Maximum: |
0.1%
|
Combined Effect (source, load, temperature and time) |
Typical: |
0.15%
|
|
Maximum: |
0.3%
|
Startup Time |
Maximum: |
1 Second
|
Any source/load
|
Recovery Characteristics |
Excursion: |
<3% of nominal output
|
50 - 100% load
|
Recovery: |
1000W: 100 μsec
1500W: 300 μsec
|
Return to 1% of setting
|
Ride through |
Minimum: |
21.5 milliseconds
|
From loss of source to flag signal.
|
Hold-up Time |
Minimum: |
5 milliseconds
|
After signal flag.
|
Overshoot |
Turn on: |
+3% maximum
|
Any source, 5% to 100% load.
|
Turn off: |
None
|
Error Sense |
3.3V, 5V: |
0.25V
|
Voltage allowance per wire.
|
All others: |
0.4V
|
Series Connection (output floats) |
|
500V
|
Maximum voltage off ground.
|
Parallel Connection (for redundancy) |
|
Current shares within 5% of rated load.
|
5 ~ 100% load, hot swappable
|
Selective Overvoltage shutdown |
|
Adjustable 100 ~ 140% of nominal; factory set to 130%.
|
Latched, reset by cycling source power off.
|
Current Limiting |
|
Constant current mode; factory set at 110% of IO max.
|
Optional shutdown mode with 20 second delay.
|
Remote On/Off |
RC-1: |
Normally high
|
Isolated form C or TTL.
|
RC-2: |
Normally low
|
Overtemperature |
|
Thermostat, auto restart.
|
With hysteresis
|