SERIES JQE GENERAL SPECIFICATIONS
|
Specification
|
Rating/Description
|
Condition
|
INPUT
|
a-c Voltage
|
105-125, 210-250V a-c
|
User Selectable (1)
|
Current
|
See Model Table
|
Max load, 115V a-c
|
Frequency
|
47-65Hz
|
Range
|
OUTPUT
|
d-c Output
|
Series pass
|
Transistor
|
Type of styabilizer
|
Voltage Stabilizer
|
Current limited
|
Voltage
|
0 to 100% of rating
|
Adjustment range for temperature 0 - 71°C
|
Current
|
0 to 100% of rating
|
Error sense
|
0.5V per load wire
|
Static voltage allowance
|
Isolation voltage
|
500V d-c or peak
|
Output to ground
|
Isolation voltage
|
500V d-c or peak
|
Output to ground
|
Leakage current
Output to ground
|
<5 microamperes
|
rms at 115V a-c
|
<50 microamperes
|
p-p at 115V a-c
|
Series connection
|
500V
|
Max voltage off ground
|
Parallel connection
|
Automatic
|
Use current mode limiting
|
Current Sharing
|
Use master/slave connection
|
Redundancy type
|
External steering diodes
|
OVP
|
Not available
|
|
Meter Accuracy |
Digital Meters (DM suffix Models) |
1% of Full Scale
|
Voltage Mode
|
1.5% of Full Scale
|
Current Mode
|
Analog Meters (M suffix models: |
3% of Full Scale
|
Voltage Mode
|
3% of Full Scale
|
Current Mode
|
CONTROL
|
Type |
Voltage: |
Fixed input, variable gain
|
|
Current: |
Differential comparison
|
|
Voltage |
Local: |
10-turn precision rheostat
|
|
Remote Analog: |
1000 Ohms per Volt or 0 to 1mA current control
|
|
Remote Digital: |
Use SN or SNR interface
|
12-bit Listen-only
|
Curent |
Local: |
Multiturn pot
|
|
Remote Analog: |
Not provided.
|
See Series ATE models.
|
Dynamics |
Normal (slow): |
dV/dt = I/C
|
See tablulated value of C in Model Table
|
Fast mode: |
Not provided.
|
See Series ATE models.
|