   SERIES JQE GENERAL SPECIFICATIONS
Specification Rating/Description Condition
INPUT
a-c Voltage 105-125, 210-250V a-c User Selectable (1)
Current See Model Table Max load, 115V a-c
Frequency 47-65Hz Range
OUTPUT
d-c Output Series pass Transistor
Type of styabilizer Voltage Stabilizer Current limited
Voltage 0 to 100% of rating Adjustment range for
temperature 0 - 71°C
Current 0 to 100% of rating
Error sense 0.5V per load wire Static voltage allowance
Isolation voltage 500V d-c or peak Output to ground
Isolation voltage 500V d-c or peak Output to ground
Leakage current

Output to ground

<5 microamperes rms at 115V a-c
<50 microamperes p-p at 115V a-c
Series connection 500V Max voltage off ground
Parallel connection Automatic Use current mode limiting
Current Sharing Use master/slave connection
Redundancy type External steering diodes
OVP Not available  
Meter
Accuracy
Digital Meters
(DM suffix Models)
1% of Full Scale Voltage Mode
1.5% of Full Scale Current Mode
Analog Meters
(M suffix models:
3% of Full Scale Voltage Mode
3% of Full Scale Current Mode
CONTROL
Type Voltage: Fixed input, variable gain  
Current: Differential comparison  
Voltage Local: 10-turn precision rheostat  
Remote Analog: 1000 Ohms per Volt or
0 to 1mA current control
 
Remote Digital: Use SN or SNR interface 12-bit Listen-only
Curent Local: Multiturn pot  
Remote Analog: Not provided. See Series ATE models.
Dynamics Normal (slow): dV/dt = I/C See tablulated value of C in Model Table
Fast mode: Not provided. See Series ATE models.
(1) Except 1/4 Rack Models which must be returned to the factory for selection.