   KHX CURRENT HARMONICS, SOURCE
   TRANSIENTS AND EMI SPECIFICATIONS
Parameter Document Specification
IMMUNITY (1)
Radiated RF
(Ampl. Mod.)
EN 61000-4-3 (2) 10V/m, 80 - 1000MHz
Radiated RF
(Pulse Mod.)
EN 61000-4-3 (2) 10V/m, 900MHz
Magnetic Field EN 61000-4-8 (2) 30A/m, 50Hz
Electrostatic Discharge EN 61000-4-2 (2) 4KV (contact)
8KV (air)
Conducted RFI EN 61000-4-6 (2) 10Vrms, 0.15 - 80MHz
Electrical Fast Transient EN 61000-4-4 (2) 2KV, Tr/Th = 5/50ns
Surge (CM, DM) EN 61000-4-5 (2) 2KV (CM) Tr/Th = 8/20μs
2KV (DM) Tr/Th = 8/20μs
EMISSIONS
Conducted RF FCC, Class A (2)
CISPR 22, Class A (2)
2KV, Tr/Th = 5/50ns
Current Harmonics EN 60555-2 and EN 61000-3-2 (2) 0 - 2KHz
(1) All immunity levels designed to meet the requirements for heavy industrial applications per EN 50082-2 using Criteria A (no operationsl effect).
(2) Designed to meet.